• Home
  • Line Sizing Chart for CellarPro Split Refrigeration Systems

Line Sizing Chart for CellarPro Split Refrigeration Systems

Model

Liquid Line Size (ODS) up to 100 feet

 

Suction Line Size by Length (ODS)

 

Minimum Suction Line Insulation Thickness (")

Up to 25 Feet

 

Between 25 and 50 Feet

 

Between 50 and 100 Feet

3000S-EC, Sh-EC, Scm, Scmr-EC

1/4   1/2   1/2   1/2   1/2

AH3500, AH4500, 4000S-EC, Sh-EC, Scm, Scmr-EC, Swc-EC, Shwc-EC

3/8   1/2   1/2   1/2   1/2

6000S-EC, Scm, Scmr-EC / AH6500S-EC

3/8   1/2   5/8   5/8   1/2

8000S-EC, Scm, Scmr-EC, Swc-EC / AH8500S-EC

3/8   5/8   5/8   7/8   5/8

AH12Sx-EC

3/8   3/4   3/4   7/8   5/8

AH18Sx-EC

1/2   3/4   7/8   1-1/8   5/8

AH24Sx-EC

1/2   7/8   1-1/8   1-1/8   5/8

Line lengths are expressed in equivalent feet = actual run length + fitting allowances.

Use only dehydrated refrigeration service tubing and refrigeration-grade fittings.

Install refrigeration tubing in accordance with local codes and ASHRAE guidelines.