8200VS: Sizing Table - Wine Cellars 1750-2500 cubic ft

55°F Cooling Capacity1

Cooling Unit Output

Low Fan Speed
6254 BTUH
Decibels
8200VS-ECX: 57
8200VS-ECC: 66

Medium Fan Speed
6438 BTUH
Decibels
8200VS-ECX: 59
8200VS-ECC: 69

Cellar Size1

 Ambient
Temperature
 Thermal Load (BTUH)
R12 R19 R30

1750

Cubic Feet

70°F5141 4860 4691
75°F537650024775
80°F561251444861
85°F584952884949
90°F608554315035
95°F632455765124
    

2000

Cubic Feet

70°F586155565372
75°F611657115466
80°F637358665558
85°F(6630)60225653
90°F(6888)61785748
95°F(7146)63355844
    

2250

Cubic Feet

70°F631759985806
75°F(6584)61605903
80°F(6853)63226000
85°F(7122)(6485)6100
90°F(7372)(6649)6199
95°F(7662)(6812)6299
 

60°F Cooling Capacity1

 

Cooling Unit Output

Low Fan Speed
6625 BTUH
Decibels
8200VS-ECX: 57
8200VS-ECC: 66

Medium Fan Speed
6950 BTUH
Decibels
8200VS-ECX: 59
8200VS-ECC: 69

Cellar Size1

 Ambient
Temperature
 Thermal Load (BTUH)
R12 R19 R30

2000

Cubic Feet

70°F5861 5556 5372
75°F611657115466
80°F637358665558
85°F663060225653
90°F688861785748
95°F(7146)63355844
    

2500

Cubic Feet

70°F(6952)66146409
75°F(7236)67866512
80°F(7520)(6959)6618
85°F(7806)(7132)6722
90°F(8092)(7304)6827
95°F(8378)(7480)6934

The upper table is shaded to show how the 8200VS cooling system will work at maintaining 55°F, and the lower how the 8200VS cooling system will work at maintaining 60°F, inside the wine cellar using various fan speeds under various thermal loads. The thermal loads are derived from assumptions about the size of the cellar; the R-value in the six cellar surfaces (ie walls, floor and ceiling) and the ambient temperature outside the cellar.

(1) The thermal loads above are calculated based on the R-Values shown for all walls and ceiling, and a concrete floor. Lower R-Values in the cellar (eg from glass doors) will increase the thermal load on the wine cellar and will require the cooling unit to operate at higher fan speeds. Warmer climates require higher insulation to enable the cooling unit to operate at lower fan speeds. To be certain that the thermal load won't exceed the capacity of the cooling unit, email your wine cellar specifications to us and we'll be glad to assist you.

Cells shaded blue indicate loads that exceed the capacity of the cooling units shown in this table.