  • Wine Cellar Split Refrigeration System: CellarPro 2000VS Cooling Capacity

2000VS: Sizing Table - Wine Cellars 200-400 cubic ft

Cooling Unit Capacity—60°F

Cooling Unit Output

Low Fan Speed
1713 BTUH
Decibels 55.5

High Fan Speed
1886 BTUH
Decibels 61.5
Decibels 56.5 (As Ducted)

Cellar Size

 Ambient
Temperature
 Thermal Load (BTUH)
R12 R19 R30

200

Cubic Feet

70°F1300 1205 1147
75°F138012531176
80°F145913011205
85°F153813491234
90°F162013981264
95°F169914461292
    

300

Cubic Feet

70°F160114821410
75°F170015421446
80°F180016021482
85°F190016621518
90°F200017231555
95°F210017831591
    

400

Cubic Feet

70°F181016761596
75°F192117441636
80°F203318111676
85°F214618791717
90°F225619461758
95°F236920151800
    

Cooling Unit Capacity—60°F

Cooling Unit Output

Low Fan Speed
1845 BTUH
Decibels 55.5

High Fan Speed
2031 BTUH
Decibels 61.5
Decibels 56.5 (As Ducted)

Cellar Size

 Ambient
Temperature
 Thermal Load (BTUH)
R12 R19 R30

200

Cubic Feet

70°F1144 1060 1009
75°F121411031035
80°F128411451060
85°F135311871086
90°F142612301112
95°F149512721137
    

300

Cubic Feet

70°F140913041241
75°F149613571272
80°F158414101304
85°F167214631336
90°F176015161368
95°F184815691400
    

400

Cubic Feet

70°F159314751404
75°F169015351440
80°F178915941475
85°F188816541511
90°F198517121547
95°F208517731584
    

The tables are shaded to show how the 2000VS cooling unit will work at maintaining 55°F (upper table) and 60°F (lower table) inside the wine cellar, using various fan speeds and thermal loads. The thermal loads are derived from assumptions about the size of the cellar, the R-value in the six cellar surfaces (ie walls, floor and ceiling), and the ambient temperature outside the cellar.

CellarPro 2000 wine cooling units are designed to maintain optimal wine storage temperatures in wine cellars up to 400 cubic feet with adequate insulation, and can be operated with the condenser exposed to conditions up to 110°F on the high fan speed.

The thermal loads above are calculated based on the R-Values shown for all walls and ceiling, and a concrete floor. Lower R-Values in the cellar (eg from glass doors) will increase the thermal load on the wine cellar and will require the cooling unit to operate at higher fan speeds. Warmer climates require higher insulation to enable the cooling unit to operate at lower fan speeds. To be certain that the thermal load won't exceed the capacity of the cooling unit, email your wine cellar specifications to us and we'll be glad to assist you.

Cells shaded blue indicate loads that exceed the capacity of the cooling units shown in this table.