Exclusively for our retail customers, we offer free shipping on most in-stock items that ship via FedEx Ground within the continental U.S. Requires a minimum order of $50. Excludes palletized items that ship on a truck via curbside or inside delivery, wine cooling units, WineKeeper products, oversized items, on-sale items, and items that ship directly from the manufacturer. May not be combined with other coupons, discounts or offers.

Please use promo code IWASHIPFREE at checkout.
Look for our "Free Shipping" burst (shown at right) on items that qualify for free shipping. If the burst is not shown on an item, it does not qualify for free shipping.


FedEx Ground Shipping Timing Map

Information Center > Buying Guides > Cooling Unit Buying Guides > 

Ducting Correction Table - Front / Cold Side

Introduction
The performance of mechanical cooling systems will be negatively impacted as ducting lengths increase, because of the reduced mass flow rate from increased static pressure. In the table, we provide correction factors for each of our cooling units when front-ducted at various duct lengths, measured in equivalent feet. The correction factor should be applied when sizing our cooling systems, if the cold air supply and return will be ducted to and from the wine cellar.

Ducting Correction Table

In addition to applying the correction factor below, you will need to add load to your box load calculation when ducting the cold side of the cooling unit. To calculate the additional load, please refer to our 8-inch duct load calculation and 10-inch duct load calculation tables. Please contact us for more information.

Correction Factor1 for Total Equivalent Feet of Ducting2

CellarPro Model

Duct Diameter

 

25

 

50

 

75

 

100

3000S / 3200VS

8"   0.99   0.97   0.95   0.93

4000S / 4200VS

8"   0.96   0.95   0.94   0.93

AH6500 / AH8500

10"   0.99   0.98   0.97   0.96

(1) The static pressure from ducting the cold air supply and return will cause the cooling unit's BTUH performance to be diminished according to the correction factors listed above. For example, CellarPro 4200VSi cooling unit, which produces 3938 BTUH at 55°F with the High Fan Speed, would produce 3741 BTUH (ie correction factor of 0.95) with total cold air supply and return ducting of 50 equivalent feet.

(2) When measuring total equivalent feet, start with the total linear feet for both the air supply and return on the COLD side. Then, add 8 feet for EVERY 90-degree turn in the ducting.